range of product |
EasyPact
|
|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100B
|
|
circuit breaker name |
Easypact EZC100B
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
AC
DC
|
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A ( 40 °C )
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
|
|
breaking capacity code |
B
|
|
breaking capacity |
10 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Ics] rated service breaking capacity |
Ics 0.625 kA 550 V AC 50/60 Hz conforming to IEC 60947-2
Ics 1.25 kA 440 V AC 50/60 Hz conforming to IEC 60947-2
Ics 1.875 kA 380 V AC 50/60 Hz conforming to IEC 60947-2
Ics 1.875 kA 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Ics 2.5 kA 110/130 V AC 50/60 Hz conforming to IEC 60947-2
Ics 2.5 kA 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
|
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
20 A ( 50 °C )
|
|
protection type |
Short-circuit protection
Overload protection
|
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1
|
|